Configuration errors are indicated by blinking Input light on the interface board. If no error lights are lit on output modules then the problem is an invalid setting of the Panel Configuration switch on the interface board. If an error light is lit on an output module, its address switch is incorrectly set for that type of panel. | Configuration errors are indicated by blinking Input light on the interface board. If no error lights are lit on output modules then the problem is an invalid setting of the Panel Configuration switch on the interface board. If an error light is lit on an output module, its address switch is incorrectly set for that type of panel. | ||
Correctly configured modules will result in a self test that activates outputs from left to right | Correctly configured modules will result in a self test that activates outputs from left to right, unless a combo board for the largest bell is at the right end of the array. | ||
* Two modules error lights do not come on (other modules do) | * Two modules error lights do not come on (other modules do) | ||
| Line 219: | Line 219: | ||
If error lights occur on output modules, the following operational errors may be indicated: | If error lights occur on output modules, the following operational errors may be indicated: | ||
* All module's error light comes on and stays on. | * All module's error light comes on and stays on. | ||
** If Bit Map mode is selected (Map configuration switches 4, 5 and 6 are all ON), a constant input data stream is | ** If Bit Map mode is selected (Map configuration switches 4, 5 and 6 are all ON), a constant input data stream is required. Check connections between the panel and controller. The interface module's Signal light should be indicating presence of the input signal. Perhaps the controller has not been configured for Bit Map mode. | ||
* One module error light comes on. The error resets when the Active state comes on next time. | * One module error light comes on. The error resets when the Active state comes on next time. | ||
** This indicates that the output pulse exceeded the | ** This indicates that the output pulse exceeded the module's maximum allowed pulse time. Reduce the pulse time on the controller (AX or Bit Map modes). Factory technicians must adjust pulse times using Chime.Center. Make sure the system has [[Network_setup_AX|Internet connectivity]] before calling for service. | ||
=== Test buttons === | === Test buttons === | ||