Set <strong>MaxAmpli</strong> to a large value like 90 to 120 (unless there are obstacles the bell might collide with) it will default to ten degrees higher than Angle before auto calculations then 5 degrees higher when testing is complete. A higher value will prevent shutdowns for exceeding the maximum angle during experimentation (error status = MaxAmpli).
Set <strong>MaxAmpli</strong> to a large value like 90 to 120 (unless there are obstacles the bell might collide with) it will default to ten degrees higher than Angle before auto calculations then 5 degrees higher when testing is complete. A higher value will prevent shutdowns for exceeding the maximum angle during experimentation (error status = MaxAmpli).


<strong>P-regulator</strong> and <strong>I-regulator</strong> both default to 50 for fully automatic calculations. Semi automatic calculations are made when they are set to equal values other than 50; in that case only the ideal I will be calculated and saved (no restart needed, P will be stored with the value you set). If the bell is easy to swing a faster semi-automatic setting will result with both P-regulator and I-regulator both set to 25. Try the default of 50 first, then change to 25 (with a strong motor) if the CalcImp mode seems to ‘hunt' for a long time. If the motor is suspected to be weak for the bell, set P-regulator to a higher value such as 75. While the bell is swinging and taking a long time to calculate the best values, and you are happy with the way the bell is swinging, you can interrupt the calculation process by setting I-regulator to zero.
<strong>P-regulator</strong> and <strong>I-regulator</strong> both default to 50 for fully automatic calculations. Semi automatic calculations are made when they are set to equal values other than 50; in that case only the ideal I will be calculated and saved (no restart needed, P will be stored with the value you set). If the bell is easy to swing a quicker semi-automatic calculation will result with both P-regulator and I-regulator both set to 25. Try the default of 50 first, then change to 25 (with a strong motor) if the CalcImp mode seems to ‘hunt' for a long time. If the motor is suspected to be weak for the bell, set both regulators to a higher value such as 75.  
 
The automatic calculations should be finished within ten minutes. If it is taking longer and you are happy with the way the bell is ringing, you can terminate the calculations using the current settings. To do this, keep the bell swinging and set I-regulator to zero. The display will change to 'Swing' and you can stop the bell. Make sure it starts correctly with the saved values after coming to a complete stop.


=== Automatic calculation ===
=== Automatic calculation ===