Bell Control Technical Data 3700: Difference between revisions
moved driver testing to repair section |
|||
| Line 186: | Line 186: | ||
If you want to reset to default pulse times | If you want to reset to default pulse times | ||
* Change the module configuration (unplug a module temporarily) and cycle power | * Change the module configuration (unplug a module temporarily) and cycle power | ||
== Other applications == | == Other applications == | ||
| Line 227: | Line 215: | ||
When replacing a module with a configuration or address switch. Make sure that the switch on the replacement module matches that of the original module before powering the panel. | When replacing a module with a configuration or address switch. Make sure that the switch on the replacement module matches that of the original module before powering the panel. | ||
=== DC Striker Module === | |||
You can use a digital multimeter to check the IGBT output drivers of the DC Striker Module. | |||
[[File:37DC-IGBT-Test.jpg|200px|thumb|right|Test outputs]] | |||
* Make sure the panel is powered off (circuit breaker or local disconnect) | |||
* Unplug the power cable from the Power Supply Module that feeds high voltage to the DC Striker Modules | |||
* Remove the output fuses from the module | |||
* Set the multimeter to Diode Junction test mode | |||
* Hold the red meter probe to the top power pin | |||
* Check the top contact of each fuse holder on the module | |||
** The voltage drop should be around 0.5 Volts - shorted outputs will be near 0 Volts (and fuse will be blown - do not replace) | |||
** Return the module to Chime Master for replacement/rework if any measurement is less than 0.35 Volts | |||
[[Category:Installation]] | [[Category:Installation]] | ||
[[Category:Troubleshooting]] | [[Category:Troubleshooting]] | ||