Bell Control Technical Data 3700: Difference between revisions

0.6.3 carillon default pulses
Fiber optic installation
Line 72: Line 72:


If shielded cable is used (recommended), connect the shield to the lower right mounting screw of the Interface Module. Do not connect the shield at the controller end.
If shielded cable is used (recommended), connect the shield to the lower right mounting screw of the Interface Module. Do not connect the shield at the controller end.
==== AX Fiber optic cable ====
Use Multi-mode Duplex cable with two ST connectors at each end. Use care when installing the cable to prevent kinks and damage to the ends. The ends should be marked by color, number or with specification text on one channel of the 'zip' cord. Whichever channel is plugged into the left STATUS of the tower panel, also connects to the left STATUS connector on the rear of the AX touch screen controller. The opposite color should be plugged into the right DATA connectors at both ends.
For multipanel carillon installations, only Panel 1 will have the optical interface. Parallel the 485 terminals of Panel 1 and the additional panel(s).


=== LX Systems ===
=== LX Systems ===