Bell Control Technical Data 3700: Difference between revisions
installation |
replacement info |
||
| Line 128: | Line 128: | ||
** The voltage drop should be around 0.5 Volts - shorted outputs will be near 0 Volts (and fuse will be blown - do not replace) | ** The voltage drop should be around 0.5 Volts - shorted outputs will be near 0 Volts (and fuse will be blown - do not replace) | ||
** Return the module to Chime Master for replacement/rework if any measurement is less than 0.35 Volts | ** Return the module to Chime Master for replacement/rework if any measurement is less than 0.35 Volts | ||
== Repairs === | |||
When replacing a module with a configuration or address switch. Make sure that the switch on the replacement module matches that of the original module before power on the panel. | |||
[[Category:Installation]] | [[Category:Installation]] | ||
[[Category:Troubleshooting]] | [[Category:Troubleshooting]] | ||