MagForce motor system installation: Difference between revisions
| Line 73: | Line 73: | ||
=== Control inputs === | === Control inputs === | ||
Swinging bell control relays in the Chime Master panel are connected to an output terminal labeled Common, M1, M2, M3 etc. for each bell output. Connect a wire from the relay panel Common to the terminal marked | Swinging bell control relays in the Chime Master panel are connected to an output terminal labeled Common, M1, M2, M3 etc. for each bell output. Connect a wire from the relay panel Common to the terminal marked L3out (three phase) or L2out (single phase) terminal of the circuit breaker in the MagForce control panel. Connect the output relay panel ''Mn'' terminal for each bell to its corresponding ''Sn'' terminal in the MagForce control panel. | ||
Weather-proof toggle switches for each bell are installed on the front panel (largest bell on the left) in parallel with these control inputs for testing in the tower when the controller is disabled. | Weather-proof toggle switches for each bell are installed on the front panel (largest bell on the left) in parallel with these control inputs for testing in the tower when the controller is disabled. | ||