Specific Relay Model Technical Data:
Relay panel technical information
Wiring color codes
All primary wiring shall be 16 AWG or greater, stranded with 600V insulation in the following colors:
- Earth protective ground - Green
- Neutral (not generally required) - White
- L1 - Black
- L2 - Red
- L3 - Blue (when three phase power is used for motors)
- T1, T2, etc. DC striker outputs (polarity not important) - Yellow
- M1, M2, etc. Motor contactor outputs (high voltage, low current) - Violet
- COM - may be jumpered to L1 at the factory - Black
Secondary low voltage control wiring shall be 18 AWG with 300V insulation in the following colors:
- Negative DC - Black
- Positive DC control - Red
Lights and test buttons
At the top of the relay panel is a square board with three buttons with four lights at the top edge.
The four lights are labeled:
Power - Data - Fault - Status
The buttons may be labeled:
Reset - Test - Step
At the bottom of this board, and sometimes installed on an auxiliary board attached with a ribbon cable, are one inch square output modules mounted vertically (up to four outputs on the main board, up to twelve outputs on the auxiliary board). For tolling outputs, there will be two timer adjustment controls. For motorized ringers there will not be adjustments. At the top of these boards is a green light that indicates the output is on. At the bottom of the board is a red light that indicates the output is driving a short circuit.
Test mode
Hold the Test button (under the Data light) while momentarily clicking the Reset button (under the Power light). After the Fault light blinks you can let go of the Test button. The Data light should remain lit to indicate the panel is in the self-test mode.
Press the Step button to sequence through the outputs. The tolling outputs will ring first then any motorized outputs will follow. Note that after ringing the Motorized outputs, the toll outputs may locked out (hammer protect mode). If you need to test the tollers again, repeat the procedure above to reset the test mode (after the bells have ceased to swing).
To repeat an output that you have stepped to, press the Test button to repeat it. This is useful for testing motorized outputs that time out after a second or so.
Exit test mode
The panel will reset to the standby mode in a couple of minutes. For immediate reset, press the Reset button so that the Data light goes out.
Pulse Adjustments
Each timer board has two adjustment potentiometers. The top adjustment sets the length of the pulse and the bottom adjustment sets the maximum repeat rate. For both cases, clockwise adjustments shorten the pulse and allows smaller bells to repeat faster.
If the lower potentiometer is adjusted clockwise more than the upper adjustment, the ON pulse will be shortened to allow faster repeats.
Pulse setting procedure for large tolling bells
- Set the top adjustment fully clockwise
- Set the bottom adjustment fully counter-clockwise
- Turn top adjustment counterclockwise until the ringing does not get any louder
Pulse setting procedure for small chime/carillon bells
- Set both adjustments fully clockwise (short pulse)
- Turn top adjustment counterclockwise until the ringing does not get any louder
- If the top adjustment is fully counterclockwise and you can get the bell to ring louder by turning the bottom adjustment farther then continue adjusting the bottom adjustment until the desired performance is obtained.
Troubleshooting
Fuse blows
Test Open Output
Disconnect output wires from PCB for the bell that blows fuse. If fuse still blows without anything connected, the rectifier is probably at fault. Most panels have socketed rectifiers that can be replaced. Be sure to align the angled corner (positive lead) correctly when inserting the replacement.
Test Alternate Output
If the output in question does not blow the fuse when its output is not connected, try connecting the bell to another output (lower numbered output for high current fuse). If the other output fuse blows there is a problem with the striker or wiring.